The PC60 is a miniature series single pole single throw contactor designed for printed circuit board mounting. Devised for both interrupted and uninterrupted loads, the PC60 is suitable for switching Resistive, Capacitive and Inductive loads. Typical applications include Telecommunication, UPS and other power conversion systems.
The PC60 features single pole double breaking main contacts with silver alloy tips, which are weld resistant, hard wearing and have excellent conductivity. The PC60 can be secured to the printed circuit board by means of an M4 bolt.
Note: The PC range now incorporates the mounting board option, previously assigned to the MB range (existing MB part numbers remain valid).
Application | ||
Thermal Current Rating | 80A | 80A |
Intermittent Current Rating: | ||
30% Duty | 145A | 145A |
40% Duty | 125A | 125A |
50% Duty | 115A | 115A |
60% Duty | 105A | 105A |
70% Duty | 95A | 95A |
Rated Fault Current Breaking Capacity (Icn) 5ms Time Constant: (In accordance with UL583*) | ||
Blowouts | 500A at 2V D.C. | |
No Blowouts | 500A at 1V D.C. | |
Rated Fault Current Breaking Capacity (Icn) Resistive Load: (In accordance with UL508*) | ||
Blowouts | 500A at 3V D.C. | |
No Blowouts | 500A at 4V D.C. | |
Maximum Recommended Contact Voltages | ||
Blowouts | 500V | 500V |
No Blowouts | 500V | 500V |
Typical Voltage Drop per pole across New Contacts at 80A | 40mV | |
Mechanical Durability | > 3,000,000 Cycles | |
Coil Voltage Available (Us) (Rectifier board required for A.C.) | 6 - 130V |
Component | Configurations |
---|---|
Auxiliary |
STANDARD
|
Coil Terminations |
PCB
|