RW1000

NO - SP - ST

The Reduced Silver series are suitable for applications where infrequent switching is specified. In such applications the degradation of the tip is minimal and therefore a higher volume of silver is unnecessary.

The RW1000 is designed for use in telecommunication and power distribution applications where an uninterrupted load is switched. These contactors are primarily for use with Direct Current loads but can also be used with Alternating Currents.

The RW1000 features double breaking main contacts with silver alloy tips which are weld resistant, hard wearing and have excellent conductivity. Silver plating on the main contacts is optional for the RW1000. This compact contactor can be busbar mounted vertically or horizontally, but if mounted vertically, the coil should be at the bottom. If the coil is required at the top, we can adjust the contactor to compensate for this.

RW1000 Technical Information

Application
InterruptedRating ( Ith )Uninterrupted
Thermal Current Rating - 1200A
Intermittent Current Rating:
30% Duty - 2190A
40% Duty - 1895A
50% Duty - 1695A
60% Duty - 1550A
70% Duty - 1435A
Rated Fault Current Breaking Capacity (Icn) 5ms Time Constant: (In accordance with UL583*)
Blowouts -
No Blowouts -
Rated Fault Current Breaking Capacity (Icn) Resistive Load: (In accordance with UL508*)
Blowouts -
No Blowouts 1800A at 60V D.C.
Maximum Recommended Contact Voltages
Blowouts - -
No Blowouts - 60V
Typical Voltage Drop per pole across New Contacts at 1200A 50mV

Mechanical Durability > 1,000,000 Cycles
Coil Voltage Available (Us) (Rectifier board required for A.C.) 6 - 240V

RW1000 Features

Component Configurations
Auxiliary
STANDARD
STANDARD - GOLD
V3
V3 - GOLD
Coil Suppression
DIODE
DIODE AND RESISTOR
Coil Terminations
AMP TAGS
FLYING LEADS
VACCUM IMPREGNATION
Mounting Options
'L' Shaped Bracket Kit