The ED150 range of switches have been designed to provide a rapid means of disconnecting batteries or other power supplies in the event of serious electrical faults. Whilst the switches are primarily intended for use with battery powered vehicles they are also suitable for use with static power systems. All types are capable of safely rupturing full load battery currents in the event of an emergency.
The ED150 is a manually operated device with a simple over-centre spring mechanism which provides a snap action for both opening and closing of the main contacts. The ED150 is easy to install (see drilling details) and is secured with supplied M5 posidrive mounting screws.
Precautions:
When fitted with magnetic blowouts the polarity marked on the contact housing must be observed when connecting the main terminals. Ensure that the switches are installed in a position where heavy arcs emanating from the switch cannot damage or electrically jump across to adjacent parts. The switch is to be used to rupture current in an emergency or as a no-load isolator.
Do not use as a regular On-Load Switching Device.
Application | ||
Thermal Current Rating | - | 150A |
Intermittent Current Rating: | ||
30% Duty | - | 275A |
40% Duty | - | 235A |
50% Duty | - | 210A |
60% Duty | - | 195A |
70% Duty | - | 180A |
Rated Fault Current Breaking Capacity (Icn) 5ms Time Constant: (In accordance with UL583*) | ||
Blowouts | 1000A at 96V D.C. | |
No Blowouts | 1000A at 48V D.C. | |
Rated Fault Current Breaking Capacity (Icn) Resistive Load: (In accordance with UL508*) | ||
Blowouts | - | |
No Blowouts | - | |
Maximum Recommended Contact Voltages | ||
Blowouts | - | 96V |
No Blowouts | - | 48V |
Typical Voltage Drop per pole across New Contacts at 150A | 40mV | |
Mechanical Durability | > 10,000 Cycles | |
Coil Voltage Available (Us) (Rectifier board required for A.C.) | 0 - 0V |
Component | Configurations |
---|---|
Auxiliary |
STANDARD
STANDARD - GOLD
|