RW800

NO - SP - ST

The Reduced Silver series are suitable for applications where infrequent switching is specified. In such applications the degradation of the tip is minimal and therefore a higher volume of silver is unnecessary.

The RW800 is designed for use in telecommunication and power distribution applications where an uninterrupted load is switched. These contactors are primarily for use with Direct Current loads but can also be used with Alternating Currents.

The RW800 features double breaking main contacts with silver alloy tips which are weld resistant, hard wearing and have excellent conductivity. Silver plating on the main contacts is optional for the RW800. This compact contactor can be busbar mounted vertically or horizontally, but if mounted vertically, the coil should be at the bottom. If the coil is required at the top, we can adjust the contactor to compensate for this.

RW800 Technical Information

Application
InterruptedRating ( Ith )Uninterrupted
Thermal Current Rating - 800A
Intermittent Current Rating:
30% Duty - 1460A
40% Duty - 1265A
50% Duty - 1130A
60% Duty - 1035A
70% Duty - 955A
Rated Fault Current Breaking Capacity (Icn) 5ms Time Constant: (In accordance with UL583*)
Blowouts -
No Blowouts -
Rated Fault Current Breaking Capacity (Icn) Resistive Load: (In accordance with UL508*)
Blowouts -
No Blowouts 1200A at 60V D.C.
Maximum Recommended Contact Voltages
Blowouts - -
No Blowouts - 60V
Typical Voltage Drop per pole across New Contacts at 800A 50mV

Mechanical Durability > 1,000,000 Cycles
Coil Voltage Available (Us) (Rectifier board required for A.C.) 6 - 240V

RW800 Features

Component Configurations
Auxiliary
STANDARD
STANDARD - GOLD
V3
V3 - GOLD
Coil Suppression
DIODE
DIODE AND RESISTOR
BI-DIRECTIONAL DIODE
Mounting Options
'L' Shaped Bracket Kit

%s Resources

RW800 Data Sheet